Static Voltage Stability Analysis In Power Systems Engineering Essay
Voltage stability, one of the principal aspects of power system stability, has been the main reason for many of major power system blackout incidents over the last few decades. It is acknowledged universally that voltage stability is and will remain a challenge in the 21st century, even likely to increase in importance. Therefore a better understanding of voltage stability in power systems is necessary for power engineers, who might participate in the planning, designing, and operation of modern power systems. This report talks about a relevant engineering thesis project: Static Voltage Stability Analysis in Power Systems, which is carried out for 2 semesters from July 2009 to June 2010.
The aim of this thesis project is to conduct a more comprehensive study into the theory of static voltage stability, and investigate a new approach for power flow analysis: 3-dimension P-Q-V curve. First of all, the basic knowledge of static voltage stability is reviewed, and analysis on an elementary power system, radial system, is carried out including power flow study, P-V and Q-V curve analysis. Based on the 2- dimension P-V and Q-V plotting, the relationship of P, Q, and V is studied and a new method for static voltage stability analysis is tried: P-Q-V curve.
The second part of this project focuses on the analysis of WSCC three-generator-nine-bus system. Simulation of the system is carried through by means of UWPFLOW and POWERWORLD. Direct power flow method and continuation power flow method are applied and the weakest bus is studied. Last but not least, curves are obtained and results are discussed.
Keywords: Static Voltage Stability; Radial System; Power Flow Method; Continuation Power Flow Method; P-V Curve; Q-V Curve; P-Q-V Curve.
CONTENTS
摘 覠i
ABSTRACT ii
CONTENTS iv
CHAPTER 1 INTRODUCTION 1
CHAPTER 2 POWER SYSTEM VOLTAGE STABILITY 8
CHAPTER 3 STATIC VOLTAGE STABILITY ANALYSIS OF ELEMENTARY POWER SYSTEM 11
CHAPTER 4 STATIC VOLTAGE STABILITY ANALYSIS OF WSCC NINE-BUS SYSTEM 26
CHAPTER 5 CONCLUSION 39
REFERENCES 41
ACKNOWLEDGEMENTS 43
APPENDIX A MATLAB CODES FOR FIGURE 3.8 44
APPENDIX B MATLAB CODES FOR FIGURE 4.2 46
APPENDIX C MATLAB CODES FOR FIGURE 4.3 47
APPENDIX D MATLAB CODES FOR FIGURE 4.4 48
APPENDIX E MATLAB CODES FOR FIGURE 4.5 49
APPENDIX F MATLAB CODES FOR FIGURE 4.6 50
APPENDIX G MATLAB CODES FOR FIGURE 4.7 51
APPENDIX H DATA OF WSCC NINE-BUS SYSTEM 52
CHAPTER 1 INTRODUCTION
An Overview of Modern Power System
A power system is a network of conductors and devices which allows electrical energy to be transferred from the generating power stations to load centers through transmission network. Since the first electric network in the United States was established at the Pearl Street Station in New York City by Thomas Edison in 1882 [1], power systems have been experiencing more than 100 years’ development and improvement. Nowadays, modern power system has developed to be a complex interconnected network, which can be subdivided into four parts:
Generation
Private and publicly owned generators produce the electricity that feeds into high voltage grids.
Transmission
High voltage transmission grids transport power from generating units at various locations to distribution systems which ultimately supply the load.
Distribution
Distribution systems deliver the power from local bulk supply points to the consumers’ service-entrance equipments.
Loads
Loads of power systems are composed of industrial, commercial, and residential load.
Figure 1.1 Modern Power System [2]
Power System Stability
A power system is said to be stable if it has the property that it retains a state of equilibrium under normal operating conditions and regains an acceptable state of equilibrium after being subjected to a disturbance. Of all the complex phenomena on power system, power system stability is the most intricate to understand and challenging to analyze [3]. Damage to power system stability may cause the system to blackout or collapse as well as other catastrophic incidents, leading to enormous social and economic losses.
Classification of Power System Stability
Based on the system’s different properties, network structures and operation modes, the system instability can behave in many different ways. Accordingly power system stability study is divided mainly into three fields: angle stability, frequency stability and voltage stability. The diagram below shows visually the classification of power system stability.
Figure 1.2 Classification of Power System Stability
History of Study on Power System Stability
Initially, angular stability was firstly paid attention to and studied since power transmission capability had traditionally been limited by either rotor angle (synchronous) stability or by thermal loading capability. And the blackout problems had been associated with transient stability, which were diminished by fast short circuit clearing, powerful excitation systems and varies special stability controls [3]. In other words, nowadays the theory and methods on angular stability are relatively more complete.
Meanwhile, study on voltage stability had been quite slow, which mainly attributed to two reasons:
Incidents caused by voltage instability or voltage collapse occurred relatively late, not until which did people paid attention to voltage instability problems.
Understanding of voltage instability was not so profound as other kinds of instability problems in the early days. Varies of issues arose during the study on voltage stability such as load-based modeling, dynamic behaviors of different components as well as their interaction, and so on.
Overview of Power System Voltage Stability
Voltage Instability Incidents in the World
Power system voltage stability was firstly introduced in 1940s, but failed to draw people’s attention until 1970s, since which voltage instability and collapse had resulted in several major system failures or blackouts throughout the world, as listed below [4, 5, 22]:
August 22, 1970, Japan, 30 minutes;
September 22, 1970, New York, several hours;
September 22, 1977, Jacksonville, Florida, few minutes;
December 19, 1978, France, 26 minutes;
August 4, 1982, Northern Belgium, 4.5 minutes;
September 2, November 26, December 28 & 30, 1982, Florida, 1-3 minutes;
May 21, 1983, Northern California, 2 minutes;
December 27, 1983, Sweden, 55 seconds;
June 11, 1984, Northeastern USA, several hours;
May 17, 1985, South Florida, 4 seconds;
April 1986, Winnipeg, Canada Nelson River HVDC links, 1 second;
May 20, 1986, England, 5 minutes;
November 1986, SE Brazil, Paraguay, 2 seconds;
January 12, 1987, Western France, 6-7 minutes;
July 20, 1987, Illinoisand India, several hours;
July 23, 1987, Tokyo Japan, 20 minutes;
August 22, 1987, Western Tennessee, 10 seconds;
July 2, 1996, Western System Coordination Council (WSCC), Northern USA;
August 1996, Malaysia;
August 14, 2003, USA & Canada;
September 28, 2003, Italy.
Progress of Study on Voltage Stability
The large numbers of worldwide voltage collapse incidents made it become the focus of world’s attention to study voltage stability of power system. In the 1982’s researching list of Electric Power Research Institute (EPRI) in USA, voltage stability was considered as the most significant issue. Over the last thirty years, and especially over about the last twenty years, utility engineers, consultants, and university researchers have intensely studied voltage stability. Hundreds of technical papers have resulted, along with conferences, symposiums, and seminars. Utilities have developed practical analysis techniques, and are now planning and operating power systems to prevent voltage instability for credible disturbances [6].
Importance of Voltage Stability in Future
In a foreseeable future, the global fast-growing power consumption will require more intensive use of available transmission facilities, which means an operation of power systems closer to their voltage stability limits. The increased use of existing transmission is made possible, in part, by reactive power compensation [6]. Undoubtedly, voltage stability is and will remain a challenge in the 21st century, even likely to increase in importance. Therefore a better understanding of voltage stability in power systems is necessary for power engineers, who might participate in the planning, designing, and operation of modern power systems.
Topic Definition and Scope
The topic of this project is Static Voltage Stability Analysis in Power Systems, which mainly focuses on the following:
Overview of the phenomena of static voltage stability;
Analysis associated with the phenomena;
Reasons why voltage collapse happens;
Measures to improve static voltage stability.
In consideration of restrictions on the simulation, a three-generator-nine-bus case is used throughout the whole project while a typical two-bus (one-generator-one-load) case is used for the P-Q-V curve analysis.
Aims and Objectives
The main objective of this project is to get a wider and deeper understanding of static voltage stability in power systems, which can be reduced into sub-objectives:
To conduct a more comprehensive study into the theory of static voltage stability;
To look for reasons why voltage collapse happens;
To investigate a new approach for power flow analysis: 3-dimension P-Q-V plotting;
To propose proper measures of improving static voltage stability in power systems;
To conclude generation direction and load direction for the analyzed power system.
CHAPTER 2 POWER SYSTEM VOLTAGE STABILITY
Basic Concepts of Voltage Stability
IEEE Definitions
IEEE [7] provided a formal definition of voltage stability and relative concepts as given below:
Voltage Stability: Voltage stability is the ability of a system to maintain voltage so that when load admittance is increased, load power will increase and so that both power and voltage are controllable.
Voltage Collapse: Voltage collapse is the process by which voltage instability leads to very low voltage profile in a significant part of the system.
Voltage Security: Voltage security is the ability of a system not only to operate stably, but also to remain stable (as for as the maintenance of system voltage is concerned) following any reasonable credible contingency or adverse system change.
CIGRE Definitions
Nevertheless, the above definitions of voltage stability conditions were not directly compatible with the general IEEE definition for stability concept. Hence new definitions were given in CIGRE report [8], which are as following:
Voltage Stability: A power system, at a given operating state and subjected to a given disturbance, is voltage stable if voltages near loads approach post-disturbance equilibrium values. The disturbed state is within the region of the stable post-disturbance equilibrium.
Voltage Instability: Voltage instability is the absence of voltage stability, and results in progressive voltage decrease (or increase). Destabilizing control reaching limits, or other control actions (e.g. load connection), however, may establish global stability.
Voltage Collapse: Following voltage instability, a power system undergoes voltage collapse if the post-disturbance equilibrium voltages near loads are below acceptable limits. Voltage collapse in the system may be either total (blackout) or partial. Voltage collapse is more complex than simple voltage instability leading to a low-voltage profile in a significant part of the power system.
Other Relative Concepts
Large-disturbance Voltage Stability: Large-disturbance voltage stability is concerned with a system’s ability to control voltages following large disturbances such as system faults, loss of generation, or circuit contingencies. The study period of interest may extend from a few seconds to tens of minutes. Therefore, long-term dynamic simulations are required for analysis.
Small-disturbance Voltage Stability: Small-disturbance voltage stability is concerned with a system’s ability to control voltages following small perturbations such as incremental changes in system load. For such case, static analysis is effectively used.
Relation of Voltage Stability to Rotor Angle Stability
Voltage stability and rotor angle (or synchronous) stability are more or less interlinked. Transient voltage stability is often interlinked with transient rotor angle stability, and slower forms of voltage stability are interconnected with small-disturbance rotor angle stability.
Voltage Stability is concerned with load areas and load characteristics. For rotor stability, we are often concerned with integrating remote power plants to a large system over long transmission lines. Voltage stability is basically load stability, and rotor angle stability is basically generator stability [6].
In a large interconnected system, voltage collapse of a load is possible without loss of synchronism of any generators. Transient voltage stability is usually closely associated with transient rotor angle stability. Long-term voltage stability is less interlinked with rotor angle stability. We can consider that if voltage collapses at a point in a transmission system remote from loads, it is an angle instability problem. If voltage collapses in a load area, it is possibly mainly a voltage instability problem.
CHAPTER 3 STATIC VOLTAGE STABILITY ANALYSIS OF ELEMENTARY POWER SYSTEM
Introduction of an Elementary Model: Radial System
Simple radial system network is used to develop most of the concepts of the static voltage stability. Once basic concepts are understood, we can represent as much as appropriate in computer simulation, which will be carried out in Chapter 4. Figure 3.1 shows an equivalent circuit of the power system, and a model called radial system is formed to represent such power system, as shown in Figure 3.2.
Figure 3.1 Equivalent Circuit of Power System
Figure 3.2 Radial System Model
The sending-end and receiving-end voltages are assumed to be fixed and can be interpreted as points in large systems where voltages are stiff or secure. The sending end and receiving end are connected by an equivalent reactance.
Basic Analysis of Radial System
Active Power Transmission
Applying the radial system in Figure 3.2, the relations can be easily calculated:
Similarly, for the sending end:
The familiar equations for and are equal since we assume a lossless system, and maximum power transferred is at a power load angle equal to 90 degree. Note that the 90-degree maximum power angle is nominal, in other words, maximum power occurs at a different angle if we apply transmission losses or resistive shunt loads. And the case with impedance load at the receiving end will be discussed in section 3.2.2.
Reactive Power Transmission
In the study of the static voltage stability in power system, the transmission of reactive power is especially of interest. Usually we are interested in variable voltage magnitudes. Particularly, we are interested in the reactive power that can be transmitted across a transmission line, or a transformer as the receiving-end voltage sags during a voltage emergency or collapse. Considering the reactive power flow over the transmission line alone, we can write approximate formulas for Equations (3.3) and (3.5) in terms of small angles by using :
From Equations (3.6) and (3.7), it can be observed that reactive power transmission depends mainly on voltage magnitudes and flows from the higher voltage to the lower voltage. Such observation, however, cannot be applied in the case of high stress, i.e. high power transfers and angles, where the angle is large enough and no longer approaches 1. This is important as voltage stability problems normally happen during highly stressed conditions.
Difficulties with Reactive Power Transmission
Reactive Power Transmission Behavior in Different Cases
First of all, take an example of the radial system in Figure 3.2, assuming X=0.2 p.u. with varied values of voltage magnitude and angles, i.e. varied loading conditions. Applying Equations (3.3) and (3.5), and can be calculated as listed in the following table:
Conditions
(p.u.)
(p.u.)
(degree)
(p.u.)
(p.u.)
Lightly loaded
1.10
1.00
10
0.634
0.416
Moderately loaded
1.05
0.90
20
1.072
0.390
Heavily loaded
1.00
0.80
50
2.429
-0.629
Table 3.1 Reactive Power Transmission in varied conditions
From the table, it is clear that at higher loading, transmission lines are more difficult to transfer reactive power and reactive power cannot be transmitted across large power angles (the value of becomes negative in the case with a power angle of 50 degree).
Minimizing Transfer of Reactive Power
High angles are due to long lines and high real power transfers. It is therefore required to maintain voltage magnitude profiles with voltages of approximately 1 p.u.. Compared with real power transfers, reactive power cannot be transmitted across long distances. It has been observed that the greater distance of the reactive power sources from the reactive demand will lead to: [9]
greater voltage gradient on the lines supplying the reactive power
greater amount of required reactive power compensation
more difficult to control the voltage level
Another reason to minimize the transfer of reactive power is minimizing the real and reactive losses. The purpose to reduce real losses is due to economic reasons while minimizing the reactive losses can reduce investment in reactive devices such as shunt capacitors.
As we know, the losses across the series impedance of a transmission line are and . For , we have:
and
Obviously, to minimize losses, we should minimize reactive power transfer and keep voltage high at the same time. Keeping voltage high to minimize reactive losses helps maintain voltage stability. In other words, reactive power should be generated close to the receiving end.
Power Flow Analysis
In a power system, powers are known rather than currents. Thus power flow analysis is backbone of static voltage stability studies. Power flow analysis, also known as load flow analysis, involves the calculation of power flows and voltages of a transmission network for specified terminals or bus conditions.
Bus Classification
In solving a power flow problem, a power system is supposed to be operating under balanced conditions and a single-phase model is used. Associated with each bus are four quantities: active power P, reactive power Q, voltage magnitude , and voltage angle.
The following types of buses (nodes) are represented, and at each bus two of the above four quantities are specified:
Voltage-controlled (P-V) buses: These buses are the generator buses. They are also known as regulated buses or P-V buses. For such kind of buses, the real power P and voltage magnitude are specified, while the reactive power Q and the voltage angle are unknown.
Load (P-Q) buses: Load buses are also called P-Q buses as their real power P and reactive power Q are specified. The voltage magnitude and angle are to be determined.
Slack (Swing) bus: Such bus is taken as reference of the whole power system. For a slack bus, the voltage magnitude and voltage angle are specified. As the power losses in the system are not known a priori, at least one bus must have unspecified P and Q. Thus the slack bus is the only bus with known voltage. This bus makes up the difference between the scheduled loads and generated power that are caused by the losses in the network [1]. Traditionally while analyzing, the voltage magnitude of slack bus is assumed to be 1 p.u. and the voltage angle is assumed to be 0 degree.
Transmission Line Modeling
The transmission line is traditionally represented with two types of models: nominal model and nominal T model, as shown in Figure 3.3 and Figure 3.4 where Z is the series impedance and Y is the shunt admittance due to the line charging capacitance. Neither nominal T or nominal À exactly represent the actual line, however, they brings great convenience in the power flow analysis, especially in the application of NEWTON-RAPHSON method, which will be discussed in the coming section.
Figure 3.3 Nominal Model
Figure 3.4 Nominal T Model
NEWTON-RAPHSON Power Flow Method
In order to include all the three types of buses (P-V bus, P-Q bus and slack bus as introduced in 3.3.1) at the same case, a 3-bus power system is considered as shown in Figure 3.5, where
Bus 1 is the slack bus, i.e. and are specified as .
Bus 2 is a voltage-controlled bus, i.e. and are known while and are unknown.
Bus 3 is a load bus, i.e. and are known while and are unknown.
Figure 3.5 3-bus Power System
The network performance equation of such a sample is:
where
Applying the bus-loading equations:
Now NEWTON-RAPHSON Power Flow Method can be approached as:
P-V Curve Analysis
P-V curve is useful for conceptual analysis of static voltage stability and for study of radial system, where P is the load in an area and V is the voltage at a critical or representative bus. Besides, P can also be the power transferred across a transmission interface or interconnection. Voltage at several busses can be plotted.
Consider the radial system as shown in Figure 3.2. The receiving-end active power can be expressed as in the Equation 3.2. Then a P-V cueve can be plotted as in Figure 3.6, which shows relationship between P and V at the receving end for different values of load power factor and the locus of the critical operting point is shown by the dotted line. Nornally, only the operting points above the locus of the critical points represent satisfying operating condition. A sudden reduction in power factor or increase in Q can thus cause the system to change from a stable operating condition to an unsatisfactory and possibly unstable [10].
Figure 3.6 V versus P for different power factors [10]
Q-V Curve Analysis
Q-V curve is presently the workhorse method of voltage stability analysis at many utilities [6]. Considering the system in Figure 3.2, we can obtain reactive power both at sending end and receiving end, or and by means of Equation (3.5) and Equation (3.3). Then a Q-V cueve can be plotted as in Figure 3.7, which shows relationship between Q and V. The reactive power margin is the MVAr distance from the operating point to either the bottom of the curve, or to a point thaere the voltage squared characteristic if an applied capacitor is tanfent to the V-Q curve [6]. Additionally, the slope of the V-Q curve indicates the stiffness of the bus.
Figure 3.7 Typical Q – V Curve
A New Method for Static Voltage Stability Analysis: P-Q-V Curve Analysis
Introduction of MATLAB Software
MATLAB is a numerical computing environment and fourth generation programming language. Developed by The MathWorks, MATLAB allows matrix manipulation, plotting of functions and data, implementation of algorithms, creation of user interfaces, and interfacing with programs in other languages [18]. An additional package, Simulink, adds graphical multi-domain simulation. This project greatly benefits from MATLAB to handle 3-dimension curve drawing for P-Q-V curve study, as well as the matrix manipulation associated with power flow analysis, 2-dimension curve plotting for P-V/Q-V curve study in the analysis of WSCC nine-bus system, which will be described in details in CHAPTER 4.
P-Q-V Curve
In this section, for convenience of forming an ideal voltage source, we assume the angle of the to be zero while the angle of to be degree. Then Equation 3.2 and 3.3 become:
Noting that
We can eliminate in Equations 3.16 and 3.17, which obtains
or
Obviously, with specified , and , Equation 3.19 shows relationship of , and . To work out such relationship visually, MATLAB is applied and a P-Q-V curve is obtained as below, where P stands for , Q stands for V stands for and E stands for . Refer to Appendix A for details on MATLAB codes, with the assumsion that E = 1 , X= 0.2 and the values of tan are chosen randomly as [-0.41, -0.2, 0, 0.2, 0.41, 1, 10, 100, 1000].
Figure 3.8 P – Q – V Curve
CHAPTER 4 STATIC VOLTAGE STABILITY ANALYSIS OF WSCC NINE-BUS SYSTEM
Introduction of WSCC Nine-bus System
WSCC nine-bus system is a typical testing system develped by Western Systems Coordinating Council. It is commonly uesd in jornals and papers for power system studying. Figure 4.1 shows an overview of the WSCC nine-bus system. Refer to Appendix H for parameters of this system.
Figure 4.1 Single Line Diagram of WSCC Nine-bus System
Introduction of UWPFLOW Software
For determining the static voltage stability of the WSCC nine-bus system, UWPFLOW software is used. This software has been developed by University of Waterloo, Canada, and distributed free on the Power Globe. It was written in C and runs under DOS and UNIX enviroments. It has no limitation on the system size other than those imposed by memory limitation in the corresponding enviroment, i.e. RAM and swap space in the UNIX and exrended memory in DOS [16, 20].
UWPFLOW is a research tool that has been designed to calculate local bifurcation characterized by a singularity in the power system Jacobian. This was developed based on power flow method. This software also generates a series of output files that allow further analysis. UWPFLOW reads AC power flow data in WSCC format [11] or IEEE common format [12], DC data in ETMSP format [13], FACTS devices data in s special format described in [14], and steady state load model data in OH format [15]. However in the present study IEEE common format data is used. Additional UN format data is required for bifurcation analysis, such as direction of generation change, direction of load change and maximum genertion limit [10]. The software assumes that one parameter the loading factor, is allowed to change. All steady state system controls remain operational unless otherwise specified by means of the software option.
Introduction of POWERWORLD Software
POWERWORLD Simulator is an interactive power system simulation package designed to simulate high voltage power system operation on a time frame ranging from several minutes to several days [17]. POWERWORLD provides a linear programming based optimal power flow package Simulator OPF, which ideally suits to do power flow analysis. What’s more, the planning-mode tool Simulator PVQV fulfills the need of Q-V curve drawing. Throughout the project, PowerWorld Simulator will be used to carry out power flow analysis and Q-V curve study of the twelve-bus case.
Analysis of WSCC Nine-bus System
Direct Method: Repeated Power Flow
First of all, the WSCC nine-bus system in Figure 4.1 is built in UWPFLOW software. By running the system and increasing the loading level of step by step, attention will be focused on getting convergence and the maximum loading level. For loading “direction”, assume all the loads are increased by the same ratio, and only generator at Bus-1 is allowed to dispatch required additional real power.
With the load P and Q increased simultaneously with the ratio of 10%, in the same loading direction, the bus voltages in per unit measurement are tabulated in Table 4.1. Couples of data points are collected near the system divergence point. Table 4.1 has shown that the system started to collapse (or diverge) at the point where all loads at the 3 load buses are increased in the same direction till 116%. Note that in Table 4.1, the starting point is denoted as 0% as there is no additional loads added, which is named as basic load. Then we can conclude from Table 4.1 that the maximum loading level for the WSCC nine-bus system is at additional of 116% loading direction on all 3 load buses.
Load Increment (%)
Bus5
Bus7
Bus9
P (MW)
Q (Mvar)
V (p.u.)
P (MW)
Q (Mvar)
V (p.u.)
P (MW)
Q (Mvar)
V (p.u.)
90
30
1.0129
100
35
1.0162
125
50
1.0261
10
99
33
1.0069
110
38.5
1.0105
137.5
55
0.9886
20
108
36
1.004
120
42
1.0053
150
60
0.981
30
117
39
0.9928
130
45.5
0.999
162.5
65
0.972
40
126
42
0.9846
140
49
0.993
175
70
0.9625
50
135
45
0.9753
150
52.5
0.9862
187.5
75
0.9516
60
144
48
0.9648
160
56
0.979
200
80
0.9394
70
153
51
0.953
170
59.5
0.9711
212.5
85
0.9257
80
162
54
0.9396
180
63
0.9626
225
90
0.9102
90
171
57
0.9242
190
66.5
0.9532
237.5
95
0.8923
100
180
60
0.9061
200
70
0.9428
250
100
0.8714
110
189
63
0.881
210
73.5
0.9239
262.5
105
0.84
112
190.8
63.6
0.8737
212
74.2
0.9167
265
106
0.83
114
192.6
64.2
0.8657
214
74.9
0.9087
267.5
107
0.8191
115
193.5
64.5
0.86
215
75.25
0.9024
268.75
107.5
0.8116
116
194.4
64.8
0.8291
216
75.6
0.8617
270
108
0.7774
Table 4.1 Loading Directions for Three Load Buses with the Corresponding Bus Voltage Obtained from Load Flow
Based on Table 4.1, the voltages against the load at each load bus are plotted by means of MATLAB, as shown in Figure 4.2. Refer to Appendix B for details on MATLAB codes.
Figure 4.2 Voltage versus Loading Direction for Each Load Bus
Determination of Weakest Bus
In order to find out the weakest bus, we consider the factor at the point closer to divergence. The load bus with the highest ratio of at the point closer to divergence is the weakest bus we are looking for. The loading point of 114% and 115% are chosen for calsulation.
For Bus5:
For Bus7:
For Bus9:
The different ratios show that Bus-9 is having the highest ratio(-0.006). In other words, Bus-9 has the steepest slope near the divergence point. Therefore Bus-9 is the weakest bus in this power system.
Power Flow Jacobian Matrix
The loads (P & Q) on Bus5, Bus7 and Bus9 are increased simultaneously by 10% each step. The Jacobian matrix of the system at each different loading direction (with the P & Q ratio as indicate on Table 4.1) is stored and processed. Matlab command “svd(Jacobian_Matrix)” is run at each iteration and the diagonal matrix/singular value matrix is captured as in Table 4.2.
Base Load
10%
20%
30%
40%
50%
60%
70%
55.7468
56.0039
55.6116
55.1815
54.7125
54.2016
53.647
53.0435
52.5551
52.5819
52.3491
52.0891
51.799
51.4751
51.1118
50.7031
51.2282
51.2252
50.8438
50.3998
49.8884
49.3032
48.6331
47.8694
48.4689
48.6036
48.4065
48.1879
47.9458
47.6764
47.3742
47.0289
46.7896
46.9571
46.7227
46.4664
46.1873
45.8816
45.5475
45.1782
39.5043
39.571
39.4605
39.3394
39.208
39.0643
38.9071
38.7337
21.1088
21.278
21.1662
21.047
20.9184
20.7804
20.6312
20.4681
17.8041
17.8209
17.7138
17.5879
17.4406
17.2703
17.074
16.8482
15.4188
15.4796
15.3359
15.189
15.0373
14.881
14.7183
14.5465
14.5018
14.4366
14.247
14.0366
13.8034
13.5441
13.2559
12.9352
12.7479
12.7591
12.6912
12.6107
12.5162
12.4081
12.2843
12.1441
10.3082
10.2513
10.1556
10.052
9.9394
9.816
9.6796
9.5276
5.8461
5.8825
5.8332
5.7785
5.7181
5.6512
5.5764
5.4932
2.2403
2.2356
2.2159
2.1949
2.1723
2.1482
2.122
2.0938
0.8676
0.8679
0.8669
0.8659
0.8647
0.8634
0.8619
0.8602
0.7954
0.7964
0.7943
0.792
0.7894
0.7865
0.7832
0.7795
0.5236
0.5243
0.5207
0.5173
0.5144
0.5117
0.5094
0.5074
Singular
0.3235
0.3219
0.3189
0.3146
0.3087
0.3011
0.2913
0.2793
Eigenvalue
0.1047
0.1036
0.1017
0.0990
0.0953
0.0907
0.0849
0.0780
Condition No
172.3240
173.9792
174.3857
175.4021
177.2352
180.0120
184.1641
189.9159
Table 4.2 Power Flow Jacobian Singular Matrix, Calculated Eigenvalues
and Condition Number
80%
90%
100%
110%
112%
114%
115%
116%
52.386
51.6654
50.8662
50.2616
49.8623
49.4269
49.9267
47.9894
50.2419
49.7165
49.1121
49.147
48.5218
47.8566
47.3268
44.0659
47.0181
46.3025
45.744
45.7964
45.4945
45.1585
44.9446
43.5596
46.6067
45.8431
44.6622
42.9582
42.455
41.9414
43.4275
41.8008
44.769
44.3075
43.7696
42.6927
42.239
41.6874
41.4478
39.376
38.5417
38.3255
38.0783
38.8683
38.7029
38.5201
41.2916
38.3606
20.29
20.0926
19.8694
19.3733
19.154
18.916
19.2077
18.2084
16.5872
16.2827
15.9235
17.2305
17.0758
16.9054
17.9452
16.7376
14.3643
14.1662
13.9465
15.3518
15.1707
14.9726
15.1777
14.4642
12.576
12.1705
11.7145
11.8599
11.7491
11.6331
11.8449
11.3517
11.9857
11.8049
11.5904
11.1698
10.9963
10.8016
11.5228
10.8796
9.3558
9.1579
8.9247
9.0324
8.911
8.7754
8.6994
8.2344
5.399
5.2912
5.1656
5.0479
4.9755
4.896
5.669
5.4017
2.0628
2.0285
1.9897
3.6567
3.6294
3.5988
4.5811
4.2192
0.8583
0.8561
0.8534
1.9055
1.8836
1.8593
2.275
2.2207
0.7753
0.7705
0.7648
0.7682
0.7652
0.7618
1.7626
1.6642
0.5058
0.5044
0.5031
0.4102
0.4091
0.4078
0.3454
0.339
Singular
0.2647
0.2469
0.2252
0.1572
0.1480
0.1377
0.0245
0.0007
Eigenvalue
0.0701
0.0610
0.0507
0.0247
0.0219
0.0190
0.0006
0.0000
Condition No
197.9071
209.2564
225.8712
319.7303
336.9074
358.9463
2037.8245
68556.2857
Table 4.2 (Cont.) Power Flow Jacobian Singular Matrix, Calculated Eigenvalues
and Condition Number
The minimum value in the diagonal matrix is the singular value of the system (the least value which may contribute to system collapse when loads increased). Figure 4.3 shows the singular value plot against the total load of the system. Refer to Appendix C for details on MATLAB codes.
Figure 4.3 Singular Value versus Loading Direction
In Table 4.2, the singular value of each iteration is squared in order to calculate the eigenvalues; the eigenvalue versus total load (increment percentage) is shown in Figure 4.4, noting that [eigenvalue = square(singular value)]. Refer to Appendix D for details on MATLAB codes.
Figure 4.4 Eigenvalue versus Loading Direction
Condition number of power flow Jacobian is obtained by dividing the highest singular value by the minimum singular value. The value of the condition number at each step of load increment is listed in Table 4.2. The plot of the condition number versus loading direction is given in Figure 4.5. Refer to Appendix E for details on MATLAB codes.
Figure 4.5 Condition Number versus Loading Direction
Reactive Power Limits of Non-slack Generators
It’s known from the power flow executed in 4.4.1 that the system started to diverge on the point when all loads increased 116%. The power flow output file of UWPFLOW is studied and the reactive power of the other 2 generators (other than slack bus) connected at bus 2 and bus 3 are as below:
Bus 2:
Bus 3:
It’s clearly seen that generators at bus 2 and bus 3 are hitting the maximum reactive power supply (by comparing the Qmax in the input file “wscc9bus.cf”). Hence, there is insufficient of reactive power provided in the system and the voltage profile collapses drastically.
Continuation Power Flow (CPF) Method
Case 1: All Load Buses Increasing at the Same Time
The voltage profiles for load buses 5, 7 and 9 with the same loading direction by using Continuation Power Flow Method is obtained in the ‘x’ matrix in the m-file specified in the input command. The voltage profiles for the three load buses are tabulated in Table 4.3. Figure 4.6 shows the P-V curve of the three load buses. Refer to Appendix F for details on MATLAB codes.
P (% in per unit)
Bus 5
Bus 7
Bus 9
1.0129
1.0162
0.99582
0.15675
1.0033
1.0078
0.98445
0.31135
0.99203
0.99865
0.97115
0.46354
0.97882
0.98875
0.95569
0.61298
0.96338
0.97797
0.93772
0.75913
0.94531
0.96616
0.91676
0.90115
0.92399
0.95312
0.89207
1.0377
0.89842
0.93851
0.86246
1.1522
0.87079
0.92381
0.83039
1.2378
0.84348
0.91024
0.79854
1.3002
0.81621
0.89754
0.7665
1.3426
0.78877
0.8856
0.73394
1.367
0.76105
0.8743
0.70059
1.3743
0.73292
0.8636
0.66611
1.365
0.70432
0.85346
0.63011
1.3388
0.6752
0.84384
0.59201
1.2942
0.64561
0.83471
0.55092
1.2283
0.61585
0.82603
0.50515
1.1331
0.58705
0.81768
0.45067
0.97432
0.56661
0.80942
0.37059
0.72636
0.6047
0.80786
0.26296
0.56151
0.64718
0.81272
0.21346
0.38855
0.68348
0.81932
0.17587
0.21464
0.71025
0.82592
0.14622
0.04105
0.72878
0.83185
0.12127
0.02046
0.73047
0.83249
0.11853
0.73208
0.83312
0.11583
Table 4.3 Load Buses Voltage Profiles Calculated in Continuation Power Flow Method
Figure 4.6 P-V Curse of Load Buses 5, 7 and 9 in the Same Loading Direction, in CPF Method
Based on Figure 4.6, the collapse point is close to 1.374 per unit (or 137.4%) loading of P. Meanwhile, the divergence point as shown on 4.4.1 is on 116%. From Table 4.3, the divergence point happened on the 13 iterations whereby the direct method requires longer time to reach the divergence point when the step size is 10%. Anyhow, the continuation power flow method has lost some accuracy as compared to the direct method in 4.4.1. The actual divergence point happened on 116% but the CPF method reaches the divergence point at 137.4%. In short, CPF method is able to provide a quick result on the divergence point of the system but losing the accuracy; direct method is slow but has the precise response.
Case 2: Only Load at Bus 9 Increased
In this case, it is assumed that only the load at bus 9 is allowed to be increased. In order to achieve such condition, the “wscc9bus.k” input file of UWPFLOW is modified. The base loads of the Bus 5 and Bus 7 are now changed to zero in the k file. The bus voltage profile for Bus 9 is listed in the x-matrix of the m-file specified. The data (voltage per unit) on Bus 9 is then tabulated in Table 4.4.
P (% in per unit)
V5
V7
V9
1.0129
1.0162
0.99582
0.38822
1.0059
1.0112
0.96971
0.76823
0.99696
1.0051
0.93943
1.1375
0.98545
0.99783
0.90386
1.4915
0.97063
0.98882
0.8611
1.8211
0.95109
0.97732
0.80763
2.0438
0.93111
0.9658
0.75491
2.1799
0.91084
0.95421
0.70245
2.2424
0.89014
0.94239
0.64919
2.2363
0.8689
0.93015
0.59418
2.1614
0.84704
0.91733
0.53636
2.0111
0.82449
0.90371
0.47433
1.7704
0.80127
0.88897
0.40598
1.4073
0.77756
0.87264
0.3277
0.85
0.75396
0.85395
0.23259
0.34368
0.73977
0.84077
0.16016
0.00034
0.73209
0.83313
0.11588
0.73208
0.83312
0.11584
Table 4.4 Load Bus 9 Voltage Profiles with Increasing Load Changes, in CPF Method
The collapse point is now found on 224% (or in 2.24 per unit) increment loading on Bus 9 while the other 2 load buses are fixed. Figure 4.7 illustrates the plot. Refer to Appendix G for details on MATLAB codes.
Figure 4.7 Bus 9 Voltage (p.u.) versus Total Loads, with Bus 5 and Bus 7 Loads Unchanged, in CPF Method
It can be seen that when Bus 9 is the only changing load bus, and the load Bus 5 and Bus 7 remain constant, the divergence point is stretched to approximately 224%. It can be concluded that with only one load change on a single bus, the reactive power of the generators is able to sustain until 224% of load increment on Bus 9 before system collapses.
CHAPTER 5 CONCLUSION
Theoretical Coverage
The initial part of the power system background provides an overview on the classification of power system stability, with relation to voltage stability, and typical issues involved in voltage instability in history. The second part focuses mainly on the voltage stability knowledge and relationship of voltage stability with the rest of power sytem. In terms of structural presentation, the theoretical background was constructed with the concept of presenting in an easy-to-understand manner by means of a variety of figures.
The third part involves an in-depth study of static voltage stability. The main focus was on the power flow analysis and P-Q-V curve analysis. In addition, the theoretical base with regards to power transimission is also discussed. All in all, the knowledge gained from the theory involved provides better understanding in the simulation portion of the thesis.
Simulation Process
The simulation process involves the WSCC nine-bus power system. Based on the simulation in UWPFLOW and POWERWORLD, direct power flow method and continuation power flow method are applied. Results are obtained from the output files and relative curves are plotted in MATLAB.
On the basis of the simulation, the following observations are made:
Maximum loading level for the WSCC nine-bus system is at additional of 116% loading direction on all 3 load buses.
With the highest ratio of at the point closer to divergence, Bus-9 has the steepest slope near the divergence point. In other wrods, Bus-9 is the weakest bus in this power system.
With only one load change on a single bus, the reactive power of the generators is able to sustain until 224% of load increment on Bus 9 before system collapses.
Continuation power flow method is able to provide a quicker result on the divergence point of the system but losing the accuracy while direct method is slower but has the precise response.
Conclusion
The large numbers of worldwide voltage collapse incidents since 1970s made it become the focus of world’s attention to study voltage stability of power system. Voltage stability, also known as load stability, is now a major concern in planning and operating power system. And in a foreseeable future, the global fast-growing power consumption will require more intensive use of available transmission facilities, which means an operation of power systems closer to their voltage stability limits. Undoubtly, voltage stability will still remain as one of the most significant issues in the researching list of power system engineering.
Order Now