Tables for refrigerant of R134a in the domestic refrigerator
CHAPTER -4
RESULTS & DISCUSSION
4.1 Experimental Procedure on Running Refrigeration Tutor
4.1.1 Tables for refrigerant of R134a in the domestic refrigerator
Table reading taken from the process of R134a refrigerant placed within the experimental setup. Note the reading of compressor water, mechanical device outlet condenser outlet, evaporator temperature pressure & of varied parameters within the setup. This is the normal domestic refrigerator having refrigerant 180 grams placed in the system.
Table 4.1.1 Reading of R134a Refrigerant without Heat Exchanger
Operating freezer point |
Time taken for 5 revolution |
T1 c |
T2 c |
T3 c |
P1 (bar) |
P2 (bar) |
P3 (bar) |
1 2 3 4 |
61:07 61:12 60:00 59:00 |
-3.7 -5.9 -9.3 -11 |
53 56.9 57.5 60 |
40 42 44 46 |
0.68 0.62 0.55 0.55 |
9.6 10.34 11.72 11.72 |
9.31 9.65 11.03 11.03 |
This is the heat exchanger domestic refrigerator having refrigerant 150 grams placed in the system, experimental setup is same & procedure is same as normal domestic refrigerator.
Table 4.1.2 Reading of R134a Refrigerant with Heat Exchanger
Operating freezer point |
Time taken for 5 revolution |
T1 c |
T2 c |
T3 c |
P1 (bar) |
P2 (bar) |
P3 (bar) |
1 2 3 4 5 6 |
46:10 49:18 50:30 49:29 51:20 53:12 |
-7.9 -7.9 -9.6 -12 -15 -17.8 |
54.8 54.9 55.6 57 58.5 59.2 |
44.3 42.3 41.6 42.6 43 43.1 |
0.68 0.55 0.58 0.58 0.37 0.344 |
17.24 15.51 15.72 15.86 15.17 15.17 |
16.55 14.62 15.03 15.17 14.48 14.48 |
4.1.2 Tables for refrigerant of R410a in the domestic refrigerator
Table 4.1.2.1 Reading for R410a without Heat Exchanger
Table reading taken from the experimental procedure of R410a refrigerant placed in the experimental setup
Operating freezer point |
Time taken for 5 revolution |
T1 c |
T2 c |
T3 c |
P1 (bar) |
P2 (bar) |
P3 (bar) |
1 2 3 4 5 6 7 |
38:12 37:59 38:90 39:10 39:38 37:59 37:34 |
-10 -10.6 -12 -14.1 -16.8 -18.7 -19.6 |
55.9 57.4 56.8 57.2 58.4 59.3 60 |
45.2 45.1 43.9 43 44 43.8 44.3 |
1.24 1.24 1.103 1.103 1.17 1.24 1.24 |
32 32 30 30 30.6 30.6 31.37 |
31.72 31.72 29.65 29.65 30.34 31 31 |
. Note down reading as per procedure placed in third chapter-3
This is the normal domestic refrigerator having refrigerant 120 grams placed in the system
Table 4.1.2.2 Reading for R410a Refrigerant with Heat Exchanger
Operating freezer point |
Time taken for 5 revolution |
T1 c |
T2 c |
T3 c |
P1 (bar) |
P2 (bar) |
P3 (bar) |
1 2 3 4 5 6 7 |
39:18 37:05 36:10 36:10 35:99 37:10 37:10 |
-10 -10 -11.5 -13.7 -15 -16.3 -18.4 |
50.7 51.7 52.3 53.1 52.9 52.3 52.7 |
41.9 42.4 42.6 42.8 42 42.1 42.2 |
1.03 1.24 1.24 1.24 1.103 1.172 1.103 |
29.3 30 30.34 31 30.68 30.68 30.68 |
28.96 29.65 30.00 30.34 30.34 30.55 30.34 |
This is the heat exchanger domestic refrigerator having refrigerant 105 grams placed in the system. Experimental setup is same & procedure is same as normal domestic refrigerator.
4.2 Calculation the Coefficient of Performance a Refrigerator Tutor
4.2.1 Calculating COP of R134a Normal & Heat Exchanger Domestic Refrigerator
Sample Calculation for R134a Normal Refrigerator:
Taking valves from table 4.1.1 of following parameter
Evaporator temperature :T1c:-9.3
Pressure (bar) : P1:0.55
Compressor temperature (outlet): T2c:57.5
Pressure (bar): P2:11.72
Condenser temperature (outlet):T3c:44
Pressure (bar): P3:11.03
Taking reading and seeing enthalpy values from the data handbook with having refrigerant R134a PH chart
Evaporator enthalpy H1:585KJ/Kg K
Compressor enthalpy H2:615KJ/Kg K
Condensed enthalpy H3:460KJ/Kg K
C.O.P :(H1-H3)/(H2-H1)
:(585-460)/ (615-585)
C.O.P:4.16
Sample Calculation for R134a with Heat Exchanger Refrigerator:
Taking valves from table 4.1.2 of following parameter
Evaporator temperature :T1c:-9.6
Pressure (bar) : P1:0.58
Compressor temperature (outlet): T2c:55.6
Pressure (bar): P2:15.72
Condenser temperature (outlet):T3c:41.6
Pressure (bar): P3:15.03
Taking reading and seeing enthalpy values from the data handbook with having refrigerant R134a PH chart
Evaporator enthalpy H1:587KJ/Kg K
Compressor enthalpy H2:617KJ/Kg K
Condensed enthalpy H3:458KJ/Kg K
C.O.P :(H1-H3)/ (H2-H1)
:(587-458)/ (617-587)
C.O.P:4.3
Refrigerating point |
-9.5 |
-13.5 |
-17.5 for H.E |
R134a without Heat Exchanger |
4.16 |
3.81 |
3.5 |
R134a with Heat Exchanger |
4.3 |
3.87 |
3.64 |
Table 4.2.1 C.O.P of R134a refrigerant with &without H.E
Figure 4.2.1 Graph Shows C.O.P of R134a refrigerant with & without H.E
4.2.2 Calculating COP of R1410a Normal & Heat Exchanger Domestic Refrigerator
Sample Calculation for R410a Normal Refrigerator:
Taking valves from table 4.1.2.1 of following parameter
Evaporator temperature :TÂ1c:-12
Pressure (bar) : P1:1.103
Compressor temperature (outlet): T2c:56.8
Pressure (bar): P2:30
Condenser temperature (outlet):T3c:43.9
Pressure (bar): P3:29.65
Taking reading and seeing enthalpy values from the data handbook with having refrigerant R410a PH chart
Evaporator enthalpy H1:434.6KJ/Kg K
Compressor enthalpy H2:441KJ/Kg K
Condensed enthalpy H3:423KJ/Kg K
C.O.P :(H1-H3)/ (H2-H1)
:(434.6-423)/ (441-434.6)
C.O.P:1.81
Sample Calculation for R410a with Heat Exchanger Refrigerator:
Taking valves from table 4.1.2.2 of following parameter
Evaporator temperature :T1c:-11.5
Pressure (bar) : P1:1.24
Compressor temperature (outlet): T2c:52.3
Pressure (bar): P2:30.34
Condenser temperature (outlet):T3c:42.6
Pressure (bar): P3:30.00
Taking reading and seeing enthalpy values from the data handbook with having refrigerant R410a PH chart
Evaporator enthalpy H1:414.9KJ/Kg K
Compressor enthalpy H2:425.4KJ/Kg K
Condensed enthalpy H3:436.4KJ/Kg K
C.O.P :(H1-H3)/ (H2-H1)
:(414.9-436.4)/ (414.9-425.4)
C.O.P:2.047
Table 4.2.2 Represent C.O.P of R410a without & With H.E
Coefficient of performance (COP) |
|||||
R410a without heat exchanger |
2.33 |
1.81 |
1.42 |
1.7 |
1.58 |
R410a heat exchanger |
3.57 |
2.04 |
1.74 |
1.83 |
1.92 |
Figure 4.2.2 Graph Shows COP Of R410a without & With H.E
4.3 Comparison of Discharge Temperature of R134 & R410a Refrigerant
4.3.1 Comparison of Discharge Temperature of R134a without & With H.E:
Following table show difference between normal & heat exchanger refrigeration tutor working of compressor discharge temperature thus shows the by using heat exchanger there is decrease in temperature . This leads to improve the performance of system compared to normal refrigerator tutor
Table 4.3.1 Shows Compressor Discharge Temperature of Normal & H.E Tutor
SNO |
EVAPORATURE TEMPERATURE OF R134a |
DISCHARGE TEMPERATURE OC |
||
1 2 3 4 |
Normal R.F |
With H.E |
Normal R.F |
With H.E |
-3.7 -5.9 -9 -11.1 |
-7.9 -9.6 -15 -19 |
55.6 56.8 57 62 |
54.8 55.6 58.5 60.1 |
|
Figure 4.3.1 Graph Shows Compressor Discharge Temperature Difference
4.3.2 Comparison of Discharge Temperature of R410a without & With H.E:
Following table show difference between normal & heat exchanger refrigeration tutor working of compressor discharge temperature thus shows the by using heat exchanger there is decrease in temperature . This leads to improve the performance of system compared to normal refrigerator tutor
Table 4.3.2 Shows Compressor Discharge Temperature of Normal & H.E System
SNO |
EVAPORATURE TEMPERATURE OF R410a |
DISCHARGE TEMPERATURE c |
||
1 2 3 4 5 |
Normal R.F |
With H.E |
Normal R.F |
With H.E |
-10 -12 -14 -16.8 -19.6 |
-10 -11.2 -15 -18 -19 |
55.9 56.8 57.2 58.4 60 |
50.7 52.3 52.9 53.5 52.7 |
|
Figure 4.3.2 Graph Shows Compressor Discharge Temperature Difference
4.4 Comparison of Refrigerator Tutor Running Time by Using Various Refrigerants in the System
4.4.1 Comparing Running Time Consumption R134a Refrigerator Tutor Without & With H.E:
When running of refrigerator tutor time calculates to get final refrigeration effect in the evaporator, when staring from end of cut-off time is taken by the refrigerator tutor.
Table 4.4.1 Time Taken for Running R134a Refrigerator Tutor without & with H.E
SNO |
EVAPORATOR TEMPERATURE POINT R134a |
TIME TAKEN GRADUALLY MINUTES |
||
1 2 3 4 5 6 |
Normal R.F 12.2 1.3 -3.7 -5.9 -7.7 -9 |
With H.E -10 -17.9 -20.1 -20.8 |
Normal R.F 10 10 10 10 10 10 |
With H.E 10 10 10 3 |
In this process found that time is decreased when tin the H.E refrigerator running time compared to normal refrigerator without H.E.
Figure 4.4.1 Graph Shows Difference of Time Taken for Running Refrigeration system
4.4.2 Comparing Running Time Consumption R410a Refrigerator Tutor Without & With H.E:
When the running mode of refrigerator tutor time calculate to get final refrigeration effect in the evaporator, when staring from end of cut-off time is taken by the refrigerator tutor .In this process found that time is decreased when tin the H.E refrigerator running time compared to normal refrigerator without H.E.
Table 4.4.2 Time Taken for Running R410a Refrigerator without & with H.E
SNO |
EVAPORATOR TEMPERATURE R410a |
TIME TAKEN GRADUALLY MINUTES |
||
1 2 3 4 |
Normal R.F |
With H.E |
Normal R.F |
With H.E |
-6.9 -14.6 -16.9 -20.1 |
0.9 -10.7 -16.4 -20.5 |
20 50 60 80 |
10 20 30 47 |
|
Figure No 4.4.2 Shows Difference of Time Taken For Running Refrigeration
4.5 Calculating Energy Consumption of Various Refrigerant using without & with H.E
4.5.1 Calculating the Energy Consumption for the Domestic Refrigerator for Running System:
By giving electric power to refrigerator tutor energy meter placed to output supply to calculate energy consumption .Taking the reading from table 4.1.1&4.1.2 evaporator, 5 revolution of energy meter in seconds. Hence calculate the energy consumption into hours.
At -9ºc freezer point time taken for 5 revolution of energy meter is 60second
Energy meter constant :1200revolution: 1 KW
:1200=3600Kj
1 revolution:3600/1200 Kj/rev
For 5 revolution :(5*3600)/ (60*1200)
Energy consumption: 0.25Kw-hr
Table 4.5.1 Reading of Energy Consumption (KW) of Domestic Refrigerator during operation
Freezer cut-off point OC |
-3.7 |
-5.9 |
-9 |
-11.1 |
R134a Without H.E |
0.2456 |
0.245 |
0.25 |
0.254 |
R134a With H.E |
0.325 |
0.298 |
0.292 |
0.288 |
Figure 4.5.1 Shows the Difference of Energy Consumption in Without & With H.E
4.5.2 Calculating the Energy Consumption for the Domestic Refrigerator for Running System:
By giving electric power to refrigerator tutor energy meter placed to output supply to calculate energy consumption .Taking the reading from table 4.1.2.1 & 4.1.2.2 evaporator, 5 revolution of energy meter in seconds. Hence calculate the energy consumption into hours.
At -10ºc freezer point time taken for 5 revolution of energy meter is 38.12second
Energy meter constant :1200revolution: 1 KW
:1200=3600KJ
1 revolution:3600/1200 KJ/rev
For 5 revolution :(5*3600)/ (38.12*1200)
Energy consumption: 0.393kw-hr
Table 4.5.2 Reading of Energy Consumption (kw) of Domestic Refrigerator during Operation
Freezer cut-off point OC |
-10 |
-12 |
-14.1 |
-16.8 |
-19.6 |
R410a Without H.E |
0.393 |
0.385 |
0.383 |
0.380 |
0.401 |
R410a With H.E |
0.382 |
0.415 |
0.416 |
0.415 |
0.404 |
Figure 4.5.2 Shows the Difference of Energy Consumption in Without & With H.E
Order Now